CO2 sensor is ideal for applications where accurate CO2 levels need to be measured and controlled for indoor air quality and energy saving applications such as demand control ventilation.
Carbon dioxide sensor - technical parameters
Measurement range: 0 to 2000 ppm (Subjecting sensors to environments less than 400 ppm for more than 15 minutes may affect accuracy)
Measuring method: Non Dispersive Infrared (NDIR), gold plated optics, diffusion sampling
Accuracy 400-2000 ppm ± 25 ppm + 3% of reading (see documentation)
Temperature dependence: 5 ppm per °C or 0.5% of the reading per °C, whichever is greater
Response time: 3 minutes for 90% step change typical
Warm up time: < 2 minutes (operational); 10 minutes (maximum accuracy)
Operation temperature: -10 až +60 °C
Size: see the picture, box height 29 mm
Mounting holes diameter: 4 mm
Conductor connection: Wago 236 terminal block
Ingress protection: IP 20
Cable length: 3 m or optional length